Liebert 1500 User Manual

Page of 59
40          Maintenance
5.3
Addition / Replacement Procedures
5.3.1
Addition or Replacement of a Rectifier 
Add a rectifier as described in the following procedure for a Helios Rectifier 100/48 or as in the 
Adding a Helios Rectifier 200I/48 or 200E/48 procedure, whichever is applicable.
LOP lamp lit
Loss of one or more phases in the AC supply
HVSD lamp lit
High voltage shutdown condition initiated by the controller
LVD lamp lit
Low voltage disconnect condition initiated by the controller
AUX 1 lamp lit
User defined alarm condition
When a Battery Disconnect Unit is present, this lamp will indicate that a 
battery disconnect alarm is ongoing.
AUX 2 lamp lit
User defined alarm condition
BOD lamp lit
Low discharge voltage condition
Incorrect BOD level adjustment
ACO lamp lit
ACO switch has been operated during an alarm condition which is still 
ongoing
EQL lamp lit
The equalize function has been activated
Rectifiers are not sharing the 
load
Incorrect float or equalize adjustment on one of the rectifiers
Sense leads opened on one rectifier
Share mode incorrectly set 
Meter display is OFF
Open meter fuse
Meter and display failure
Meter and display rotary switch in the OFF position
!
WARNING
PRECAUTIONS SHALL BE TAKEN TO AVOID SERVICE 
INTERRUPTIONS
WHEN INSTALLING A RECTIFIER, THE FLOAT AND EQUALIZE 
VOLTAGES MUST BE SET ACCORDING TO THE TYPE OF 
BATTERIES USED WITH THE SYSTEM. FAILURE TO SET 
THESE VOLTAGES PROPERLY MAY RESULT IN BATTERY 
UNDERCHARGING OR OVERCHARGING AND/OR BATTERY 
DAMAGE.
!
WARNING
PROTECTING PERSONNEL AGAINST ELECTRICAL SHOCKS
INPUT VOLTAGES TO THE RECTIFIERS ARE AT A 
DANGEROUS LEVEL. ENSURE THAT THE CIRCUIT BREAKERS 
ARE LOCKED IN THE OFF POSITION AT THE AC SERVICE 
PANEL BEFORE ATTEMPTING TO WORK ON THE RECTIFIERS. 
DANGEROUS VOLTAGES MAY STILL BE PRESENT AT THE 
TERMINALS EVEN IF THE RECTIFIERS ARE OFF. USE A 
VOLTMETER TO VERIFY FOR THE PRESENCE OF SUCH 
VOLTAGES. DO NOT SWITCH CIRCUIT BREAKERS TO ON 
UNTIL INSTRUCTED TO DO SO IN THE APPROPRIATE 
PROCEDURE.
Table 39
Fault diagnosis
Fault symptom
Possible causes