Powerware UPS20-30kVA User Manual

Page of 52
22
UPS 20-30 kVA, 230 V 0/60 Hz output  
User’s Guide
1026743 
Revision B
7.  Software and connectivity
The Software Suite CD-ROM that is bundled with the UPS contains software distributions and 
documentation in CD format. Furthermore, the comprehensive connectivity option portfolio 
includes Web/SNMP adapters for networked environments, Modem card for 24/7 remote 
monitoring, ModBus/Jbus card for building management system integration, relay interface 
cards for industrial and facilities use and RS-232 cards for serial communication to one or 
multiple computers.
Communication cables
It is recommended that the control cables and power cables be installed on separate trays. 
Where control cables will cross power cables make sure they are arranged at an angle as near 
to 90 degrees as possible. 
All control cables shall preferably be shielded. If the shield is grounded, this shall take place on 
only one end of the cable. 
The procedure for connecting the control cables is the following:
1. 
Remove the door by opening locks and lifting the door away of its original position.
2.  Locate the control terminal or XSlot module where you want to install the communications 
cable.
Figure 9 Location of control cable terminals and LCD display: 1:Graphical LCD; 2:XSlot-1; 3:XSlot-2; 4:
Signal inputs (X44 &X45); EPO (NC (X12) & NO (X52)); RS-232 (X53); Relay output (X57).