Powerware UPS20-30kVA User Manual

Page of 52
26
UPS 20-30 kVA, 230 V 0/60 Hz output  
User’s Guide
1026743 
Revision B
e)  Request Normal 
If active the UPS transfers to inverter operation if not prohibited by EPO or alarm condition. 
f) 
Force Bypass
 
If active the UPS is forced to static bypass operation regardless of the bypass status.
g)  External Battery Breaker Status 
If active the UPS knows that the batteries are disconnected. 
h)  Building alarm 1-6 
These can be activated separately or at the same time with other building alarms.
i) 
Not in use (default)
j) 
Shutdown 
If active the UPS will shutdown immediately.
k)  Delayed Shutdown 
If active the UPS will shutdown after user configurable delay time. Restart initiated 
immediately when inactive.
l) 
Normal/Bypass 
If active the UPS transfers to bypass if ok. If inactive the UPS transfers to inverter when 
possible.
m)  Output transformer over temperature 
If active the UPS output turns off after user configurable delay time.
n)   Input transformer over temperature without bypass 
If active the UPS will start to operate on battery or shutdown when batteries not available 
after one minute delay.
o)   Input transformer over temperature with bypass 
If active the UPS will start to operate on battery or transfer to bypass after one minute delay.
XSlot communication
XSlot modules allow the UPS to communicate in a variety of networking environments and 
with different types of devices. The UPS incorporates two (2) empty XSlot communication bays. 
Figure 12 Location of empty XSlot bays.