9.  Maintenance
All operations inside the unit must be performed only by a service engineer from the 
manufacturer or from an agent, authorised by the manufacturer.
The troubleshooting procedure gives simple remedial if a malfunction occurs in the UPS. 
The operator should start the trouble shooting if there is an active alarm indicated on the LCD 
screen. Service should be contacted if the active alarm is abnormal and displayed as a service 
code.
Call service if you are not able to solve the problem.
LCD display
Description
Action
Overload
The connected load needs more power 
than the UPS is rated to provide. The 
inverter or static bypass is supplying the 
excessive load level.
Shut down the least important load that 
is connected to the UPS. The UPS should 
switch back to normal operation once the 
load level is acceptable.
Battery test failed
Your batteries are detected to be faulty.
Batteries should be replaced and you need 
to contact the local office or representative 
of the UPS manufacturer.
Battery low
The UPS is operating in stored energy 
mode. It will shut down soon due to low 
battery voltage.
Make controlled shutdown of the protected 
load immediately to prevent loss of data.
On battery
The UPS is operating in stored energy 
mode.
Save your data and perform a controlled 
shutdown of your load.
Overtemperature
High UPS temperature is detected.
Check that fans are operational and 
ventilation holes are not blocked. Make 
sure the ambient temperature is not 
excessive
Table 6 Typical alarms displayed in the LCD screen of the UPS unit.
Regular service/intervals
The UPS requires very little maintenance if installed in an appropriate environment. In order 
to ensure maximum availability of the UPS, manufacturer recommends signing a proactive 
service agreement with a local authorised service provider.
Maintenance
Interval
Batteries change
~ 3-5 years / service
Batteries test
~ 18 months / service
Cooling fan change
~ 5 years / service
Table 7 Routine maintenance intervals recommended by the manufacturer.