Powerware UPS20-30kVA User Manual

Page of 52
0
UPS 20-30 kVA, 230 V 0/60 Hz output  
User’s Guide
1026743 
Revision B
13. Technical data
Standards
UPS
20 kVA
30 kVA
Safety
IEC 62040-1-1, EN 62040-1-1 and EN 60950
EMC
EN 50091-2
Product
IEC 62040-3 and EN 62040-3
Environment
UPS
20 kVA
30 kVA
Amb. temperature
0 to +40°C (electronics), 15 to +25°C (batteries)
Relative humidity
0 to 95%, no condensation allowed
Altitude
<1000 m above sea level
Vibration
IEC 68-2-6; max. 0.3 mm (2 to 9 Hz), max. 1 m/s2 (9 to 200 Hz) sinusoidal
Maintenance configuration
UPS
20 kVA
30 kVA
Dimensions
- Width
- Depth
- Height
494 mm
762 mm
1684 mm 
Weight
- no battery
- 36 battery
- 72 battery
- 108 battery
- 144 battery
200 kg
300 kg
400 kg
500 kg
600 kg
Colour
RAL 9005 black
Characteristics
Powerware 9155
20 kVA
30 kVA
Efficiency 
- nominal load
 
Up to 93%
 
Up to 93%
Heat losses
<1600 W
<1900 W
Backup time
 
- load pf 0.7  
- temperature 25°C
5  min (36 bat 9Ah) 
13 min (72 bat 9Ah) 
22 min (108 bat 9Ah) 
31 min (144 bat 9Ah)
7 min (72 bat 9Ah) 
13 min (108 bat 9Ah) 
20 min (144 bat 9Ah)
Noise (ISO 7779)
50 - 53 dB(A) depending on the load  
50 - 53 dB(A) depending on the load