UNDERSTANDING UPS OPERATION
EATON Powerware
®
 9395 UPS (1000–1100 kVA) Installation and Operation Manual  
S
  164201764 Rev 1 www.powerware.com
6−17
6.5
Multiple UPS Distributed Bypass System Oneline Configurations
The distributed bypass system oneline drawings in this section show the simplified
internal structure of the UPS, battery supply, and basic maintenance bypass in a
multiple UPS configuration. These onelines do not show each UPM in the UPSs, but
represent each UPS in the distributed bypass system. The internal structure of each
UPS is shown in Figure 6-5 through Figure 6-8 starting on page 6−7.
Oneline Drawing
UPS Model
Voltage
System Type
Input
Output
9395−1100/1000
9395−1100/1100
9395−1100/650
9395−1100/750
9395−1100/825
480
480
Multiple UPS – Distributed Bypass
1+1 and 2+0 Configurations
9395−1100/1000
9395−1100/1100
9395−1100/650
9395−1100/750
9395−1100/825
480
480
Multiple UPS – Distributed Bypass
2+1 and 3+0 Configurations
9395−1100/1000
9395−1100/1100
9395−1100/650
9395−1100/750
9395−1100/825
480
480
Multiple UPS – Distributed Bypass
3+1 and 4+0 Configurations