UPS OPERATING INSTRUCTIONS
EATON Powerware
®
 9395 UPS (1000–1100 kVA) Installation and Operation Manual  
S
  164201764 Rev 1 www.powerware.com
7−24
7.4.6
Transfer from Normal to Bypass Mode and Shut Down all UPSs
To transfer the critical load to Bypass mode and shut down all UPSs:
1.
Transfer the critical load to bypass by performing the procedure in
paragraph 7.4.4.
2.
Press the 
CONTROLS
 pushbutton on the main menu bar. The System Status
screen is displayed.
3.
On the System Status screen, select the 
UPM
 command.
4.
On the UPS Control Command screen, select the 
UPM 1
 command.
5.
Press the 
CONTROLS
 pushbutton on the System Status menu bar. The UPM 1
Control Command screen is displayed.
6.
On the UPM 1 Control Command screen, select 
UPM OFF
.
7.
Press the 
SELECT
 pushbutton on the UPM 1 Command menu bar.
The UPM status indicates 
SHUTDOWN
The input, output, and battery contactors
open, and the power module is turned off. The bypass source supplies the critical
load.
8.
UPM 2
 to shut down UPM 2.
9.
UPM 3
 to shut down UPM 3.
UPM 4
 to shut down UPM 4.
W
 
A
 
R
 
N
 
I
 
N
 
G
Power is present inside the UPS cabinet sections.
7.4.7
Single UPM Shutdown
To shutdown a single UPM:
1.
Press the 
CONTROLS
 pushbutton on the main menu bar. The System Status
screen is displayed.
2.
On the System Status screen, select the the UPM Command. The UPS Control
Command screen is displayed.
3.
On the UPS Control Command screen, select the the UPM to shutdown.
4.
Press the 
CONTROLS
 pushbutton on the System Status menu bar. The UPM
Control Command screen is displayed.