5−1
Chapter 5
Installing Options and Accessories
5.1
Installing an Optional Powerware Hot Sync CAN Bridge Card
As an option, a Powerware Hot Sync Controller Area Network (CAN) Bridge Card,
shown in Figure 5-1, can be installed to provide connectivity for operational mode
control of a parallel system. In addition, this card can be used to connect optional
system monitoring devices, such as a Remote Monitor Panel II, a Relay Interface
Module II, or a Supervisory Contact Module II to the UPS.
Plug−in Terminal
Block J3
Figure 5-1. Powerware Hot Sync CAN Bridge Card
NOTE  Only one Powerware Hot Sync CAN Bridge Card can be installed in the UPS. Multiple CAN cards are
not supported and will cause system conflicts.
To install the card:
1.
Verify the UPS system is turned off and all power sources are removed. See
Chapter 7, UPS Operating Instructions," for shutdown instructions.
2.
3.
Figure 5Table 5