Powerware 10001100 kVA User Manual

Page of 174
INSTALLING OPTIONS AND ACCESSORIES
EATON Powerware
®
 9395 UPS (1000–1100 kVA) Installation and Operation Manual  
S
  164201764 Rev 1 www.powerware.com
5−8
Table 5-4. Pull−Chain Wiring Terminations with MOBs
From
To
Function
UPS 1 CAN Bridge Card J3–1 (Alarm)
MOB 1 Aux 1 NC
MOB Open Alarm
UPS 1 CAN Bridge Card J3–2 (Alarm Return)
MOB 1 Aux 1 Com
UPS 1 TB2–1 (Pull Chain)
MOB 1 Aux 2 NO
Pull Chain
UPS 1 TB2–2 (Pull Chain Common)
UPS 2 TB2–2 (Pull Chain Common)
Pull Chain Common
UPS 2 CAN Bridge Card J3–1 (Alarm)
MOB 2 Aux 1 NC
MOB Open Alarm
UPS 2 CAN Bridge Card J3–2 (Alarm Return)
MOB 2 Aux 1 Com
UPS 2 TB2–1 (Pull Chain)
MOB 2 Aux 2 NO
Pull Chain
UPS 2 TB2–2 (Pull Chain Common)
UPS 3 TB2–2 (Pull Chain Common)
Pull Chain Common
UPS 3 CAN Bridge Card J3–1 (Alarm)
MOB 3 Aux 1 NC
MOB Open Alarm
UPS 3 CAN Bridge Card J3–2 (Alarm Return)
MOB 3 Aux 1 Com
UPS 3 TB2–1 (Pull Chain)
MOB 3 Aux 2 NO
Pull Chain
UPS 3 TB2–2 (Pull Chain Common)
UPS 4 TB2–2 (Pull Chain Common)
Pull Chain Common
UPS 4 CAN Bridge Card J3–1 (Alarm)
MOB 4 Aux 1 NC
MOB Open Alarm
UPS 4 CAN Bridge Card J3–2 (Alarm Return)
MOB 4 Aux 1 Com
UPS 4 TB2–1 (Pull Chain)
MOB 4 Aux 2 NO
Pull Chain
MOB 1 Aux 2 Com
MOB 2 Aux 2 Com
Pull Chain MOB Common
MOB 2 Aux 2 Com
MOB 3 Aux 2 Com
MOB 3 Aux 2 Com
MOB 4 Aux 2 Com