Powerware 380/220V User Manual

Page of 72
INSTALLATION
EATON Powerware
®
 Energy Management System (EMS) Upgrade Kit User’s Guide  
S
  164201724 Rev 1
 www.powerware.com
32
4.
Configure the following settings for the selected panel:
Panel Setting
Description
Panel Rating
Specify the panel breaker rating (in amps).
NOTE  Setting the panel breaker rating to 0 silences all
main panel breaker alarms and zeroes the panel percent
current levels.
Panel Warn (%)
Specify the warning threshold level (in percent load).
Panel Alarm (%)
Specify the alarm threshold level (in percent load).
Num Brkr Positions
Specify the number of breakers in the panel.
Panel Name
Specify a panel name (up to 19 characters).
Panel Serial Number
Specify the panel’s serial number (up to 19 characters).
Panel Layout
Specify the panel numbering style.
NOTE  Changing panel layout erases all branch circuit
breaker configurations.
NOTE  To revert any changes made on the current page back to default settings before
saving, click 
Reload Panel Config
.
5.
Click Save Panel Config to save the settings to the EMS−UGK.
Depending on communication speed, updates take effect within
15–20 seconds.
6.
7.
Click the Breaker Config tab to display the Breaker Settings page.
The tool automatically updates the default breaker schedule with
the latest information from the EMS−UGK. Depending on
communication speed, updates take effect within 15–20 seconds.
8.
Select the Panel Number of the panel containing the breakers to
configure. The tool automatically updates the selected breaker
schedule with the latest information from the EMS−UGK.
Depending on communication speed, updates take effect within
15–20 seconds.