INSTALLATION
EATON Powerware
®
 Energy Management System (EMS) Upgrade Kit User’s Guide  
S
  164201724 Rev 1
 www.powerware.com
33
9.
The selected breaker is highlighted in bold in the schedule. The
breaker’s configuration details display in the right half of the page.
Click the breaker to configure. The breaker number highlights and
its details display at right.
10. Configure the following settings for the selected breaker:
Breaker Setting
Description
Num Phases
Specify the number of phases (1–3).
Breaker Rating
Specify the branch breaker rating (in amps).
Warning Level
Specify the warning threshold level (in percent load).
Alarm Level
Specify the alarm threshold level (in percent load).
CT Ratio
Specify the current transformer ratio (75A).
NOTE  The selected ratio converts to the value 71.9.
NOTE  To revert any changes made on the current page back to default settings before
saving, click 
Reload Breaker Config
.
panel.
12. Click Save Breaker Config to save the settings to the EMS−UGK.
remaining panels.
14. Click Disconnect to disconnect from the EMS−UGK. Verify that Not
Connected" displays at the bottom of the page.
15. Close the software configuration tool and remove the configuration
cable.
16. Activate the reset switch on the bottom of the electronics module:
hold the switch for 10 seconds or until the display (if installed) turns
off, then release the switch.