Powerware 9315 (200 kVA---300 kVA) Operation
164201036 Rev. D 041500
Using Features and Options
The many standard features of your UPS provide consistent, economical,
and dependable power protection. In addition, you can add available options
and accessories to enhance the performance of your UPS system. This chapter
provides detailed descriptions of some of the features and options introduced
earlier in this manual.
Building Alarm Monitoring
This standard feature lets you connect the UPS to your building alarms, such as
smoke detectors or overtemperature alarms. The terminals for external
connections are located inside the UPS on the customer interface panel
(see Figure 18).
TB1
BLDG ALARM 1
BLDG ALARM 4
BLDG ALARM 5
NOTE:
All building alarm inputs or remote
features require an isolated, normally
open contact or switch (rated at 24 Vdc
20 mA minimum) connected between
the alarm input terminal and common
terminal as shown. All control wiring,
relay, and switch contacts are customer
provided.
1
2
3
4
5
6
7
8
9
15
10
11
14
13
12
TB2
BLDG ALARM 2
BLDG ALARM 3
BLDG ALARM 6
1
2
3
4
5
6
7
8
9
15
10
11
14
13
12
RS232
RS485
ON BYPASS
BATTERY CONTACTOR CLOSED
RELAY 2 NC
ON INV
RELAY 2 NO
RELAY 1 NC
RELAY 1 NO
BLDG ALARM 1 RTN
BLDG ALARM 4 RTN
BLDG ALARM 5 RTN
BLDG ALARM 2 RTN
BLDG ALARM 3 RTN
BLDG ALARM 6 RTN
REMOTE EPO
REMOTE EPO RTN
ON BYPASS RTN
BATTERY CONT RTN
ON INV RTN
ALARM RTN
NOTICE RTN
Figure 18. External Connections for Building Alarm Monitoring
Regardless of how you assign the building alarms, they display as Building Alarm 1,
Building Alarm 2, Building Alarm 3, etc., on the LCD screen of the Monitor Panel. You
should use twisted pair wires for each alarm input and common.