Powerware 9315 User Manual

Page of 92
57
Powerware 9315 (200 kVA---300 kVA) Operation
164201036 Rev. D 041500
Remote Notification
Remote Notification provides the user with the option of receiving
alarms and notices at a remote location. Remote Notification also provides some
basic controls that can be performed remotely on the UPS. Remote Notification
operates through a standard computer modem. Using the Terminal mode, the user
calls the UPS to perform basic monitoring and control. In the event of a UPS alarm
or notice, the user is notified at the remote location. The UPS calls, through the
modem, to the user’s computer or pager and leaves a message.
Remote Notification is an extension of the Terminal mode with the additional
support algorithms necessary to control an external modem (refer to Chapter 7,
“Serial Communications”). Connection to the UPS is made when a user calls the
UPS on the phone. The user has exactly the same capabilities as if using a
terminal connected directly to the UPS RS---232 port. Remote Notification differs
from the basic Terminal mode with the addition of Call Answer, Call Out, and
Housekeeping functions. The Call Answer function allows the user to call into the
UPS from a remote location and enter Terminal mode. The Call Out function allows
the UPS to be configured to call either a remote computer or numeric paging
service over the phone line. Call Out allows the UPS to call a remote computer and
leave a one-line descriptive message of the alarm or notice condition. Numeric
paging support allows the UPS to call a paging service and send numeric
messages. The Housekeeping function maintains the link between the UPS and
modem.