UPS 8 – 15 kVA, 230V 50/60 Hz output
User’s Guide
1022403
Revision  B1
23
Figure 25.
To minimise safety risk remove + or - cable from battery string before connecting
UPS and EBCs.
SPM tie cabinet
The System Parallel Module (SPM), provided by UPS manufacturer, has input connections up
to three parallel UPS modules. It is also possible to use two parallel UPS modules and one
bypass connection. This bypass option can be used for service or test purposes.
Note!
It is not allowed to feed the load simultaneously from mains (bypass) and inverter(s) of
the UPS unit(s). While turning the switch, where the bypass is connected, ON/OFF, UPS
should be on static bypass mode or shut down.
Note!
The maximum load supported by the system is limited to size of one UPS if there are
two UPSs and bypass connected to SPM.
Terminals of the SPM have two-wire connection (L1 and N) and ground terminals. The upper
ground terminal is for a load cable and the lower ground terminal is for UPSs. The wiring shall
be done according to the following wiring diagrams. The terminals and cable routing is shown
in Figure Cable routing of the SPM. See also Table 14 for cable and fuse ratings for the different
UPS ratings.