Installing a Remote EPO Control
The Remote EPO control arrives as shown in Figure 6. See Drawing
164201261---7 in Appendix A for enclosure dimensions, side views, and
knockout patterns.
EMERGENCY OFF
UNINTERRUPTIBLE POWER SYSTEM
to UPS
to other equipment
Figure 6. Remote EPO Control
To install a Remote EPO control:
1.
Securely mount the Remote EPO station. Recommended locations include
operator’s consoles or exit doors.
2.
Install wiring from the Remote EPO station using ½-in. conduit through the
7/8
-in. knockout in either the top or bottom of the UPS.
3.
Connect the Remote EPO wiring as shown in Tables A and B:
Table A. Remote EPO Wire Terminations
From REPO Station(s)
To Communications
Panel in UPS
Remarks
TB1---4
TB2---1
Twisted wires (2)
TB1---5
TB2---2
Twisted wires (2)
14---18 gauge