Powerware 5075 kVA User Manual

Page of 162
30
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation
164291261 Rev. F 111503
Before installing an RMP, be sure you have prepared the UPS according to the
instructions in Chapter 2.
To install an RIM:
1.
Securely mount the RIM.
2.
Install wiring from the RIM using ½-in. conduit through the
7/8-
in. knockout in
either the top or bottom of the UPS cabinet.
The top entry connection requires installation of ½-in. flexible conduit within the
UPS. Bottom entry connection requires no additional routing of conduit within
the UPS.
3.
If not already installed, locate the RMP adapter cable assembly (see Figure 11)
in the spare parts kit. Mate the DB---9 connector on the back of the terminal
block into the DB---9 connector on the Communications Panel of the UPS (see
Figure 12). Use two screws from the spare parts kit to secure the terminal
block bracket to the Communications Panel.
Connect to
Port 1 (DB---9) on
Communications Panel
TERMINAL
BLOCK
FUSE
(TB3)
Figure 11. Terminal Block Bracket