7.2.8
Load Off Screen
The Load Off screen (Figure 7-6) is displayed when the LOAD OFF pushbutton is
selected from the main menu bar, the UPS Control Command screen, or the Bypass
Control Command screen. This screen allows the LOAD OFF process to be aborted if
the LOAD OFF pushbutton was pressed accidentally. For Load Off procedures, see
paragraph 7.3.10 on page 7−17.
HOLD  LOAD  OFF  BUTTON  FOR  3  SECONDS
TO  TURN  OFF  LOAD
LOAD  OFF
CANCEL
Figure 7-6. Load Off Screen