7.3.10
Using the UPS LOAD OFF Pushbutton or Command
A UPS Load Off is initiated by the 
LOAD OFF
 pushbutton from the main menu bar, the
Load Off command on the UPS Control Command screen, or Load Off command on
the Bypass Control Command screen. The UPS 
LOAD OFF
 controls the UPS output by
powering down the UPS and de-energizing the critical load.
The UPS (including Bypass) remains off until restarted.
To use the 
LOAD OFF
 pushbutton:
1.
Press the 
LOAD OFF
 pushbutton.
The Load Off screen is displayed, providing a choice to proceed or abort the
shutdown.
C
 
A
 
U
 
T
 
I
 
O
 
N
All power to the critical load is lost when the LOAD OFF is selected in the following step. You should use this
feature only when you want to de-energize the critical load.
2.
To shut down the UPS, press 
LOAD OFF
 from the Load Off menu bar, and hold for
three seconds. To abort the shutdown, press 
CANCEL
.
When LOAD OFF is selected and held for three seconds, the input, output,
battery, and bypass backfeed contactors open, and the power module is turned
off.
C
 
A
 
U
 
T
 
I
 
O
 
N
Do not attempt to restart the system after Load Off until the cause of the shutdown has been identified and
cleared.
3.
To restart the UPS after pressing the 
LOAD OFF
 pushbutton, follow the procedure
W
 
A
 
R
 
N
 
I
 
N
 
G
Power is present inside the UPS cabinet sections until the upstream input feeder circuit breaker is opened.
To use the 
LOAD OFF
 command:
1.
Press the 
CONTROLS
 pushbutton on the main menu bar. The System Status
screen is displayed.
2.
On the System Status screen, select either the 
UPS
 or the 
BYPASS
 command.
3.
Press the 
CONTROLS
 pushbutton on the System Status menu bar. The UPS or
Bypass Control Command screen is displayed.
4.
On the Control Command screen, select 
LOAD OFF
.
5.
Press the 
SELECT
 pushbutton on the Command menu bar.
The Load Off screen is displayed, providing a choice to proceed or abort the
shutdown.