 9395 UPS (650–825 kVA) Installation and Operation Manual  
S
  164201725 Rev 2 www.powerware.com
8−1
Chapter 8
Communication
8.1
X−Slot Cards
The Powerware 9395 UPS has four standard, factory-installed X−Slot communication
bays. See Figure 4-27 on page 4−32 for bay locations. The UPS is compatible with the
following X−Slot cards (see Figure 8-1):
S
Modbus Card – provides direct integration of UPS information (meters and status)
to a Building Management System (BMS) using the Modbus RTU protocol.
S
ConnectUPS−X Web/SNMP Card – provides remote monitoring through a Web
browser interface, e-mail, and a network management system (NMS) using SNMP;
connects to a twisted-pair Ethernet (10/100BaseT) network. It has a built−in
switching hub that allows three additional network devices to be connected to the
network without the requirement of additional network drops.
NOTE  The Modem Card cannot be installed in X−Slot 2.
S
Modem Card
 – provides out-of-band" remote notification and monitoring using
modem communication directly to cell phones and pagers.
S
Relay Interface Card (AS/400) – has isolated dry contact (Form−C) relay outputs for
UPS status:  Utility failure, Low battery, UPS alarm/OK, or On bypass when
interfacing with IBM AS/400 computers, other relay connected computers, and
industrial applications.
S
Industrial Relay Card (IRC) – indicates the operating status of the UPS system
using the customer’s monitoring equipment. The IRC uses four isolated
normally−open or normally−closed dry relay contacts to indicate the UPS status.
Normal, Bypass, Battery, and Alarm modes can be monitored.
S
Powerware Hot Sync CAN Bridge Card – provides connectivity for operational
mode control and metering of a parallel system at any UPM in the system. In
addition, this card can be used to connect optional system monitoring devices,
such as a Remote Monitor Panel II (RMP II), a Relay Interface Module II (RIM II), or
a Supervisory Contact Module II (SCM II) to the UPS.
S
Power Xpert
®
 Gateway Card – provides a data gateway from the UPS to the Power
Xpert software; provides remote monitoring through a Web browser interface,
e−mail, and a network management system using SNMP; connects to a
twisted−pair Ethernet (10/100BaseT) network. Modbus TCP support provides direct
integration of the PDU’s parameters to a Building Management System (BMS). It
has a built−in switching hub that allows one additional network device to be
connected to the network without the requirement of an additional network drop.
Figure 8Table 8