Powerware 650825 kVA User Manual

Page of 192
UPS SYSTEM INSTALLATION
EATON Powerware
®
 9395 UPS (650–825 kVA) Installation and Operation Manual  
S
  164201725 Rev 2 www.powerware.com
4−28
4.8.2
Battery Power Wiring
C
 
A
 
U
 
T
 
I
 
O
 
N
To install wiring to connections:
NOTE  An installed FI−UPM is always designated as UPM 4.
1.
Route the battery cables between the ISBM section and the battery system or
battery disconnect. See Figure 4-18, Figure 4-20, Figure 4-25, and Figure 4-26 for
wiring access information and terminal locations.
2.
3.
Using hardware from the external wiring terminal hardware kit (see Table 3-10 on
page 3−14
), connect the positive, negative, and ground DC power wiring from the
battery system or disconnect to the ISBM section battery and ground terminals.
Use both sets of terminals shown in Figure 4-25 as needed. See paragraph 3.2.2
on page 3−8 for wiring and termination requirements.
4.
5.
6.
After wiring the UPS system to the facility power and critical load, be sure to
ground the system according to local and/or national electrical wiring codes.
7.
8.
When all wiring is complete, reinstall the top and bottom safety shield panels
removed in paragraph 4.8.1, Step 2 on page 4−18. Secure with the retained
hardware.
9.