Installing a REPO Switch
A latching−type Remote Emergency Power−off (REPO) switch can be used in an
emergency to shut down the UPS and remove power to the critical load from a
location away from where the UPS is installed. Figure 4-34 shows a REPO switch.
NOTE  Before installing a REPO switch, verify that the UPS was installed according to the instructions in
paragraphs 4.2 through 4.9.
NOTE  When installing the REPO switch, you must install conduit between the device and the UPS cabinet
for wiring the switch.
NOTE  Remove the UPS cabinet interface entry conduit landing plates to drill or punch holes
(see Figure 4-18 on page 4−20).
NOTE  The REPO switch must be a normally−open or normally−closed latching-type switch not tied into any
other circuits.
NOTE  This procedure is intended to be used for the installation of the Eaton Corporation−supplied REPO
switch. If installing another manufacturer’s switch, use this procedure only as a guide.
NOTE  The REPO switch wiring must be in accordance with NEC Article 725 Class 2 requirements.
To Install a REPO switch:
1.
Verify the UPS system is turned off and all power sources are removed. See
Chapter 7, UPS Operating Instructions," for shutdown instructions.
2.
Securely mount the REPO switch. Recommended locations include operator’s
consoles or near exit doors. See Figure 3-10 on page 3−7 for enclosure
dimensions and wiring knockouts.
3.
4.
Remove the door. Remove the retaining screw located inside the door at the
bottom hinge pivot point, then lift the door off. Retain the hardware for later use.
Contact Block (Back View, Faceplate Removed)
REPO Switch (Front View)
Figure 4-34. REPO Switch