Powerware 9315 UPS User Manual

Page of 84
9−1
EATON Powerware
®
 9315 UPS (200–300 kVA) Operation Manual  
S  164201036 Rev G  www.powerware.com
Chapter 9
Product Specifications
The UPS systems are housed in freestanding, double-front cabinets with safety shields
behind the doors. The UPS systems are available in 50/60 Hz with various output power
ratings. Smaller models within a system may be upgraded in the field to larger models:
Table 9-1. Model Numbers
System
Models
Notes
Powerware 9315 300
225 and 300 kVA
60 Hz only
Powerware 9315 250
200 and 250 kVA
50/60 Hz (400V models only)
Powerware 9315 225
225 kVA
60 Hz only
Powerware 9315 200
200 kVA
50/60 Hz (400V models only)
The following sections detail the input, output, environmental, and battery specifications
for the UPS.
Table 9-2. System Input
Operating Input
Voltage
(Nominal +10/–15%)
480 Vac for operation from 408 Vac to 528 Vac (60 Hz only)
400 Vac for operation from 340 Vac to 440 Vac (50/60 Hz only)
600 Vac for operation from 510 Vac to 660 Vac (60 Hz only)
Operating Input
Frequency Range
"3 Hz of nominal (50 Hz or 60 Hz)
Operating Input
Current
Battery Charge
125% of full load for overload + battery charge
Actual load + 25% of full load for battery charge with 0.8 pF
output units
115% of full load for overload + battery charge
Actual load + 15% of full load for battery charge with 0.9 pF
output units
Reduced for Generator
Adjustable, set to 102%
Input Current
Harmonic Content
10% THD at full load (with input filter option installed)
Power Walk-In
Adjustable 3–60 second rectifier ramp-up to full utility load
Power Factor
Minimum 0.95
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4