9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C
Chapter 15
Product Specifications
15.1 Model Numbers
The UPS systems are housed in free-standing cabinets with safety shields behind the doors.
The UPS systems are available in 50/60 Hz with various output power ratings.
System
Models
Frequency
Powerware 9390-40
40 kVA
50/60 Hz
Powerware 9390-50
50 kVA
50/60 Hz
Powerware 9390-60
60 kVA
50/60 Hz
Powerware 9390-80
80 kVA
50/60 Hz
The following sections detail the input, output, environmental, and battery specifications
for the UPS.
15.2 Single Module Specifications
15.2.1 UPS System Input
Operating Input Voltage
(Nominal +10/–15%)
208 Vac for operation from 177 Vac to 229 Vac
480 Vac for operation from 408 Vac to 528 Vac
Operating Input
Frequency Range
¦
5 Hz
Operating Input Current
See Appendix A, Table E through Table H.
Reduced for Generator
Adjustable
Input Current Harmonic
Content
5% THD at full load
Power Factor
Minimum 0.99
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4
Battery Voltage
384 Vdc (208V units only)
432 Vdc
480 Vdc