Powerware 9390 User Manual

Page of 206
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
164201535---2
1 of 2
PHYSICAL FEATURES AND REQUIREMENTS
111504
B
Installation Information
A-3
Powerware
®
9390 UPS (40–80 kVA) Installation and Operation Manual S 164201535 Rev C
1.
The UPS equipment operating environment must meet weight requirements shown in
Table A and the size requirements shown on Drawing 164201535---9.
2.
The UPS cabinet is palleted separately for shipping.
3.
Do not tilt cabinets more than
á
10˚ during handling.
4.
Dimensions are in millimeters (inches).
5.
The cabinet can be installed in
line---up–and–match or standalone configurations.
Table A Equipment Weight
Table A. Equipment Weight
Component/Model
Weight
kg (lb)
Component/Model
Shipping
Installed
Point Loading
UPS Cabinet/9390---40 kVA, 208V/208V
313 (690)
290 (640)
4 at 72.5 (160)
UPS Cabinet/9390---40 kVA, 480V/480V
271 (618)
258 (568)
4 at 64.5 (142)
UPS Cabinet/ 9390---50 kVA, 208V/208V
313 (690)
290 (640)
4 at 72.5 (160)
UPS Cabinet/ 9390---50 kVA, 480V/480V
271 (618)
258 (568)
4 at 64.5 (142)
UPS Cabinet/9390---60 kVA, 208V/208V
313 (690)
290 (640)
4 at 72.5 (160)
UPS Cabinet/9390---60 kVA, 480V/480V
271 (618)
258 (568)
4 at 64.5 (142)
UPS Cabinet/9390---80 kVA, 208V/208V
313 (690)
290 (640)
4 at 72.5 (160)
UPS Cabinet/9390---80 kVA, 480V/480V
271 (618)
258 (568)
4 at 64.5 (142)
6.
The clearances required around the UPS cabinet are shown in Table B.
Table B. UPS Cabinet Clearances
From Top of Cabinet
Minimum clearance over the UPS cabinet is
457.2 mm (18 in.) for ventilation
From Front of Cabinet
36 inches working space
From Back of Cabinet
None Required
From Right Side of Cabinet
None Required
From Left Side of Cabinet
None Required