5.2.1.  nciLocation (Location Label)
Configuration property, Node Object 0000_20 (Optional)
SNVT type: SNVT_str_asc (36)
SCPT reference: SCPT_location (17)
It can be used to provide physical location information.
- Valid Range:
Any NULL (“ 0”) terminated ASCII string of 31 bytes total length. In fact 30 bytes are available
because Null terminator has to be set the last byte.
- Default Value:
The default value is an ASCII string containing all Null (“ 0”).
5.2.2.  nviRequest (Object Request)
Input network variable, Node Object 0000_20 (Mandatory)
SNVT type: SNVT_obj_request (92)
This is the variable to request the node status response. L
ON
W
ORKS
 option unit supports some requests
shown in the table below.
Value Request
Description
0
RQ_NORMAL
If the device was in the disabled state, this request cancels that
state, and returns the functional block to normal operation.
1
RQ_DISABLED
It requests the specified functional block to change to the
disabled state. This request always brings the motor to a
controlled stop.
2
RQ_UPDATE_STATUS
It requests the status of the functional block to be sent to the
“nvoStatus” output network variable. The state of the functional
block is unchanged.
5
RQ_REPORT_MASK
It requests a status mask reporting the status bits that are
supported by the functional block to be sent to the “nvoStatus”
output network variable. A one bit in the status mask means that
the device may set the corresponding bit in the object status
when the condition defined for that bit occurs.
7
RQ_ENABLE
This request enables the system, without starting any action in
the system (no spinning of motor, etc.)
9
RQ_CLEAR_STATUS
It requests all status and report bits for the functional block and in
the “nvoStatus” output network variable to be cleared. The state
of the functional block is unchanged.
10
RQ_CLEAR_ALARM
It requests the alarm state of the functional block to be cleared. If
any alarm conditions are still present for the functional block, the
alarms are reported again as they are detected. If the Object
request does not change, reset will only be performed once.
N.B.: In case that receiving the invalid request, optional unit sets “1” to “invalid_request” bit of
“nvoStatus” output network variable.