6.3.  Network variable list (the other)
The other network variables are shown in the table below.
.
LIU
007Z
LIU
006Z
Variables
SNVT_type.
unit
Default value
v
nviResetFault
SNVT_switch
0.5%,1
{0.0%, 0}
v
nviInvSetFreq
SNVT_freq_hz
0.1Hz
3276.7Hz = invalid
v
nvoStatusWord
SNVT_state
boolean
v
nvoDrvFeedback
SNVT_switch
0.5%,1
v
nvoInvOutFreq
SNVT_freq_hz
0.1Hz
v
nvoDrvAlarm
SNVT_switch
0.5%,1
v
nvoAlarmWord
SNVT_state
boolean
---
nvoDrvThermal
SNVT_lev_percent
0.005%
---
nvoMotorThermal
SNVT_lev_percent
0.005%
v
nvoTorque
SNVT_lev_percent
0.005%
v
nvoDrvEnergy
SNVT_elec_kwh_l
0.1kWh
v
nvoDigitalIn1
SNVT_switch
0.5%,1
v
nvoDigitalIn2
SNVT_switch
0.5%,1
---
nvoDigitalIn3
SNVT_switch
0.5%,1
---
nvoDigitalIn4
SNVT_switch
0.5%,1
---
nvoDigitalIn5
SNVT_switch
0.5%,1
---
nvoDigitalIn6
SNVT_switch
0.5%,1
---
nvoDigitalIn7
SNVT_switch
0.5%,1
---
nvoDigitalIn8
SNVT_switch
0.5%,1
---
nvoDigitalInput
SNVT_state
boolean
---
nvoAnalogIn1
SNVT_lev_percent
0.005%
v
nvoAnalogIn2
SNVT_lev_percent
0.005%
---
nvoAnalogIn3
SNVT_lev_percent
0.005%
v
nviRelay1
SNVT_switch
0.5%,1
{0.0%, 0}
---
nviDigitalOut1
SNVT_switch
0.5%,1
{0.0%, 0}
---
nviDigitalOut2
SNVT_switch
0.5%,1
{0.0%, 0}
---
nviDigitalOutput
SNVT_state
boolean
{0,0,...,0}
---
nviAnalogOut1
SNVT_lev_percent
0.005%
0.000%
---
nviAnalogOut2
SNVT_lev_percent
0.005%
0.000%
v
nviEmergOverride SNVT_hvac_emerg
binary
v
nvoEmergStatus
SNVT_hvac_emerg
binary
v
nviParamCmd
SNVT_preset
binary
v
nvoParamResp
SNVT_preset
binary
v
nvoTypeVer
SNVT_str_asc
Ascii
v
nciPwUpOutTm
SNVT_time_sec
0.1s
0.0s
v: Support, ---:Not support,