Toshiba TOSVERT VF-FS1 Series User Manual

Page of 38
E6581373
- 25 -
- Valid range
LIU007Z
LIU006Z
Bit
Terminal
Parameter
Terminal
Parameter
0
---
---
1
---
---
2
---
---
3
---
---
4
---
---
5
---
---
6-15
---
---
If multiple digital output control signals are used at the same time, the output value is the OR of all digital
output controls.
6.5.7. nviAnalogOut1,2 (Control of Analog output)
Input network variable (Reserved)
SNVT type: SNVT_lev_percent (81)
They enable the analog output control.
- Valid range: 0.000 to 100.000%
(Output value is not adjusted by the inverter parameter “fm”, ”am”)
- Unit: 0.005% (The resolution depends on the inverter specification)
When the variables will be used, the inverter parameters must be assigned.
LIU007Z
LIU006Z
Name
Terminal
Parameter
Terminal
Parameter
nviAnalogOut1
---
---
nviAnalogOut2
---
---
6.5.8. nviEmergOverride (Emergency stop)
Input network variable
SNVT type: SNVT_have_emerg (103)
It provides an emergency stop of the motor. Emergency stop can be configured by Emergency stop
selection (f603) to coast stop, slow down stop or emergency DC braking (refer to the inverter
instruction manual for details).
- Valid range
Value
Command
Description
0
Remove emergency EMERG_NORMAL (No Emergency mode)
1
EMERG_PRESSURIZE (Emergency pressurize mode)
2
EMERG_DEPRESSURIZE (Emergency depressurize mode)
3
EMERG_PURGE (Emergency purge mode)
4
EMERG_SHUTDOWN (Emergency shutdown mode)
5
EMERG_FIRE (Emergency fire mode)
6 to 255
Emergency stop
---
N.B.: “Remove emergency” command clears a fault and resets the inverter.
Under Development
Under Development