Toshiba PDP002Z User Manual

Page of 28
E6581343  ③ 
- 14 - 
PNU (the parameter number) 
PNU R/W 
data 
type 
Note 
915 R/W 
Array 
[10] 
 
Unsigned16 
PNU 915, IND 1 = the inverter parameter f831 
PNU 915, IND 2 = the inverter parameter f832 
PNU 915, IND 3 = the inverter parameter f833 
PNU 915, IND 4 = the inverter parameter f834 
PNU 915, IND 5 = the inverter parameter f835 
PNU 915, IND 6 = the inverter parameter f836 
916 R/W 
Array 
[10] 
 
Unsigned16 
PNU 916, IND 1 = the inverter parameter f841 
PNU 916, IND 2 = the inverter parameter f842 
PNU 916, IND 3 = the inverter parameter f843 
PNU 916, IND 4 = the inverter parameter f844 
PNU 916, IND 5 = the inverter parameter f845 
PNU 916, IND 6 = the inverter parameter f846 
918 R 
Unsigned16 
Station 
address monitor (same as the inverter parameter f853).
927 R/W 
Unsigned16 
Operator 
control rights (parameter identification, PKW). 
Value
: Mode
 
0
Parameters cannot be written, only read   
(927 can be written). 
1: Parameters can be written and read (default). 
928 
R/W 
Unsigned16 
Control rights (process data, PZD). 
Value
: Mode
 
0: PZD part is disabled. 
i.e. Receipt of new PZD data is ignored. 
1: PZD part is enabled (default). 
929 
Unsigned16 
Selected PPO-type (same as the inverter parameter f830) 
Value: PPO TYPE 
1: PPO TYPE 1 
2: PPO TYPE 2 
3: PPO TYPE 3 
4: PPO TYPE 4 
939 R/W 
Unsigned16 
OUT1 output terminal selection (same as f130). 
Monitor is enabled using Status word bit 11. 
940 R/W 
Unsigned16 
OUT2 output terminal selection(same as f131). 
Monitor is enabled using Status word bit 12. 
941 R/W 
Unsigned16 
FL output terminal selection (same as f132). 
Monitor is enabled using Status word bit 13. 
942 R/W 
Unsigned16 
OUT3 output terminal selection (same as f133). 
Monitor is enabled using Status word bit 14. 
943 R/W 
Unsigned16 
OUT4 output terminal selection (same as f134). 
Monitor is enabled using Status word bit 15. 
947 R 
Array 
[64] 
 
Unsigned16 
Fault number 
PNU 947, IND    1 = fc90 (Active fault) 
PNU 947, IND    9 = fe10 (Last ackn. fault) 
PNU 947, IND 17 = fe11 (Second last ackn. fault) 
PNU 947, IND 25 = fe12 (Third last ackn. fault) 
PNU 947, IND 33 = fe13 (Fourth last ackn. fault) 
963 
Unsigned16 
Detected baud rate (same as f854): 
0 =    12 Mbit/s 
1 =   
6 Mbit/s 
2 =   
3 Mbit/s 
3 =    1.5 Mbit/s 
4 =    500 kbit/s 
5 =   187.5 kbit/s 
6 =   93.75 kbit/s 
7 =   45.45 kbit/s 
8 =    19.2 kbit/s 
9 =    9.6 kbit/s 
255 = Invalid baud rate 
964 R 
Unsigned16 
Identification number of the PDP002Z (0x093C) 
965 
Octet String2 
Profile number of the PDP002Z (0x0302) 
967 R 
Unsigned16 
Control 
word 
968 R 
Unsigned16 
Status 
word