Guide Specification – 3-Phase Static Uninterruptible Power Supply 
 
 
2.3  System Operation: 
The UPS shall operate as a fully automatic on-line system in the following modes: 
2.3.1 Normal 
IGBT Rectifier converts AC input power to DC power for the inverter and for charging the 
batteries. The IGBT inverter supplies clean and stable AC power continuously to the critical 
load.  The UPS Inverter output shall be synchronized with the bypass AC source when the 
bypass source is within the AC input voltage and frequency specifications. 
2.3.2 Loss of Main Power 
When Main Power is lost, the battery option shall automatically back up the inverter so there 
is no interruption of AC power to the critical load.  
2.3.3 Return of Main Power 
The system shall recover to the operating mode in Item 1 and shall cause no disturbance to 
the critical load while simultaneously recharging the backup battery. 
2.3.4 Transfer to Bypass AC source 
If the UPS becomes overloaded, or an internal fault is detected, the UPS controls shall 
automatically transfer the critical load from the inverter output to the bypass AC source 
without interruption.  When the overload or internal warning condition is removed, after a 
preset “hold” period the UPS will automatically re-transfer the critical load from the bypass 
to the inverter output without interruption of power to the critical load.  
2.3.5 Maintenance Bypass 
An optional manual make-before-break maintenance bypass panel may be provided to 
electrically isolate the UPS for maintenance or test without affecting load operation. 
 
GENERAL CONDITIONS FOR INSTALLATION 
 
3.1  Required Output Capacity:  
The UPS will be available in the following output capacities:  80, 100, 160, and 225 kVA (72, 90, 
144, and 202.5 kW).  Each unit shall be capable of being operated either independently or 
connected in parallel for a total of up to four like-capacity units.  
 
3.2  UPS Environment: 
3.2.1 Standard Environmental Parameters  
 
Operating Temperature 
 
: 32° to 104°F  (0° to 40°C) 
 
Operating Humidity   
 
: 5 - 90% (Non-condensing) 
 
Altitude 
 
 
 
: 7380 ft. (2250 m) (without derating) 
 
3.2.2 Discharge Heat from UPS  at full load. 
 
80 kVA 
 
 
 
:  11,307 Btu/Hr 
 
100 kVA 
 
 
 
:  14,133 Btu/Hr 
 
160 kVA 
 
 
 
:  19,408 Btu/Hr 
 
225 kVA 
 
 
 
:  27,292 Btu/Hr