H. Input / Output EMI / RFI Filters 
 
 
 
 
 
2.3 
System Operation 
 
 
 
The UPS shall operate as an on-line, fully automatic system in the    
 
 
following modes: 
 
 
 
A. NORMAL - Incoming AC power is boosted using a chopper circuit,  
and converted into DC power.  The DC power is then used to charge the 
battery  bank  while  at  the  same  time  providing  clean,  DC  power  to  the 
inverter circuitry.  The inverter converts DC power to regulated AC power 
which feeds the load. 
 
B.  EMERGENCY  -  Upon failure  of commercial AC power, the UPS shall 
derive  power  from  the  battery  bank  and  continue  feeding  the  load  with 
clean,  regulated  AC  power.    There  is  no  interruption  to  the  critical  load 
upon failure or restoration of commercial AC power. 
 
C.  RECHARGE  -  Upon  restoration  of  the  commercial  AC  source,  the 
rectifier/chopper  powers  the  inverter  while  simultaneously  recharging  the 
battery bank.  The UPS shall have the following recharge process:  
a)  a  constant  level  of  current  is  used  to  recharge  the  batteries  (the 
process  shall  utilize  a  current-limit  function  to  prevent  overcharging 
batteries, thus extending the life of the batteries) 
b)  as  the  batteries  reach  the  normal  charge  level,  a  constant-voltage 
control  shall  begin  which  causes  the  battery  recharge  current  to 
gradually decrease 
c)  Under normal operation, the UPS battery bank "floats" at the 2.25-2.27 
volts  per  cell  DC  level  to  stay  fully  charged  and  ready  for  the  next 
discharge.   
 
D.  BYPASS  MODE  -  Upon  detection  of  an  internal  fault  or  output 
overload,  the  UPS  shall  automatically  switch  from  inverter  power  to  an 
internal  bypass  via  the  static  switch.    Transfer  shall  be  within  4 
milliseconds, causing no interruption to the critical load.  While in bypass, 
the UPS shall protect against spikes and common/normal mode noise by 
utilizing a dual-winding output isolation transformer.  “Return from Bypass 
mode”  shall  be  an  automatic  function,  without  interruption  to  the  critical 
load.  Transfer to Bypass may also be performed as a manual operation 
via the UPS front panel. 
 
E.  POWER  CONDITIONING  MODE  -  Should  the  batteries  be  removed 
from  the  UPS,  the  UPS  shall  continue  to  function  and  still  provide