Toshiba 4200FA CT/XT User Manual

Page of 68
TOSHIBA 
 
 
4.5 Communication 
Interface 
4.5.1 
Remote Contact  
 
This interface is a standard feature and is available as dry switch contacts through a DB9 
 
male connector located on the front of the UPS.  The following schematic shows the 
 
contact state and pin assignment for each signal and the associated DB9 connector pin- 
 out. 
 
 
5 System Common  
6 Bypass Active 
Fault Signal Detect 
8 UPS On-line 
7 Battery Voltage Low 
Battery Discharge 
DB9 Male Connector Outline 
(facing connector) 
1      2      3      4     5 
 6      7      8      9        
Notes:  
 
1)  Pin “switches” are shown in their inactive states.  Example: (if battery voltage is low, pin 7 will be 
connected to System Common). 
 
2)  Contacts are rated at 30 VDC, 0.1 amps; 125 VAC, 3 amps. 
 
3)  Pin number “3” is not used. 
 
4200FA CT/XT User’s Manual 
 
 