5.5 4200FA 50kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries 
 
 
 
Model Number 
T42F3F500XAMBN 
T42F3F500##MBN 
 
Rated Output Capacity 
50 kVA 
 External 
Dimensions 
W x D x H  (cm) 
35.5” X 38.3” X 59.3”  
(90.1 cm x 97.2 cm x 150.6 cm) 
Rated Voltage 
208 VAC 
Voltage Variation 
+10% to -30%; (-15% to -30%) **** 
Rated Frequency 
50 / 60 Hz 
Input Cables Required 
3 phase ; 4 Wire + GND 
Dual Input Option Cables required 
3 phase ; 4 Wire + GND 
* Power Factor 
Greater than 0.98 when in inverter mode 
Required Input kVA 
46 kVA 
Walk-in Function 
From 20% to 100% over 5 seconds 
Inrush Current 
Less than 8 times the rated current under synchronous operation 
Current Limit 
115% maximum 
Input 
* Harmonic Currents 
Less than 3% THD 
DC Nominal (Voltage Range) 
288 VDC (216 to 332 VDC) 
Float Charge (Regulation) 
324.0 VDC (
± 2%) 
Ripple Voltage 
0.5 V R.M.S. 
**Rated Back-up Time 
5 min. at full load 
Battery 
Rated Charge Current 
11.5 Amps 
Rated Voltage 
208 / 120 VAC 
Rated Current 
138.9 Amps 
Rated Power Factor 
0.8 lagging 
Output Cables Required 
3 phase ; 4 Wire + GND 
Voltage Regulation (phase-phase) 
± 2% (0–100% balanced load);  
± 3% (0–100% unbalanced load) 
Voltage Adjustment Range 
± 5V Manually from key pad 
Phase Displacement 
± 2° (0–100% balanced load);  
± 4° (unbalanced load) 
Rated Frequency 
50 / 60 Hz 
Frequency Regulation 
± 0.1% in free running mode 
Frequency Synchronous 
± 0.5/1.0/1.5 Hz (± 1.0 Hz. std.) 
switch selectable by qualified technician 
Frequency Slew Rate 
1 Hz/s to 3Hz/s(in 0.5 Hz steps) 
Voltage Transients 
(Recovery time: 50 ms) 
± 5% (100% load step change); 
± 3% (loss or return of input voltage); 
± 8% (transfer of bypass to inverter) 
Inverter Overload Capacity 
125% 90 sec; 150% 30 sec 
Bypass Overload Capacity 
1000% 10 ms; 125% 10 min. 
Crest Factor 
2.5–3.0 within the kW range 
Neutral Line Conductor 
1.73 (200%) times line rating 
Harmonic Voltage Distortion 
1.5% max (linear load) 
Output 
Inrush Current protection 
Automatic Transfer to bypass, then retransfer to inverter 
Efficiency (Typical) 
AC/DC/AC: 88%; DC/AC: 89% 
Heat loss to be removed 
17,611 BTU/hr   (4,437 kcal/hr) 
Audible Noise 
~65dB @ 1 meter from the front of the unit 
Operating Temperature 
32 – 104 
°F (0 – 40 °C); optimal temperature is 77 °F (25 °C) 
Operating Humidity  
30–90% RH (non condensing) 
Environment 
Altitude *** 
Less than 2000 meters 
Items marked with an (*) are specified at rated conditions under balanced linear loads. 
(**) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site, and an initial 
charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation. 
(***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations). 
(****) Prolonged operation at this level requires some derating of the output capacity. 
4200FA CT/XT User’s Manual 
 
 
35