Battery Backup Time and Discharge Process 
 
The UPS system, when used in conjunction with a TOSHIBA designed Battery System, is 
 
designed to provide several minutes of back-up time (Refer to the Battery System Manual 
 
for back-up times). These times are valid when the unit is operating under full load. When 
 
these models are operating at half load, the batteries can provide approximately 2 times 
 
the specified value. The exact length of these times will depend on the UPS model used, 
 
condition of the batteries, amount and type of load, temperature and other variables. 
 
 
CAUTION 
Contact TOSHIBA when using other than TOSHIBA designed Battery Systems 
to determine proper compliance. Using other systems could void Warranty and 
or Safety Certifications. 
 
The following illustration graphically shows the battery discharge process at full load 
conditions. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
6.6 
Battery Low Voltage Tolerances  
Excessive discharge will cause the UPS battery voltage to drop bellow tolerable levels. The 
chart shown below lists the voltage level at which each UPS unit's low-voltage alarm will 
sound, and also at what level the low-voltage condition will cause the unit to automatically 
shut down. 
 
Models 
15/25/30/50 kVA 
Nominal Voltage 
288 VDC 
Alarm Voltage 
252 VDC 
Shutdown Voltage min. 
216 VDC 
 