The following list shows intervals for periodic maintenance and replacement of certain UPS 
 parts. 
 
1)  Batteries:  VRLA (Valve Regulated Lead Acid) batteries do not require the adding 
of water or electrolyte. The charging voltage, temperature, performance and 
connection resistance must be monitored periodically.  Necessary corrective 
maintenance must be made in order to assure the UPS supplies safe reliable 
power.  These items affect the life of batteries, so replacement should be once 
every 3 to 5 years as a minimum.  All of the batteries must be replaced at the 
same time to eliminate the possibility of multiple failures due to resistances of the 
batteries. 
8)  
9) 
 
  Recommended Quarterly Maintenance
 
 
 
A. Visual Checks 
1) Leakage 
2)  Corrosion on positive terminal 
B.  Check battery temperature at the negative terminal 
C.  Measure and record the system float charging voltage. 
D.  Measure and record the individual unit’s float charging voltage. 
 
Recommended
 Semi-Annual maintenance 
A.  Repeat the quarterly checks. 
B.  Perform impedance checks on the individual batteries. 
C.  Optionally test for the purpose of trending the battery over time. 
D.  Re-torque all inter-battery connecting hardware (if applicable). 
 
2) Aluminum 
electrolytic 
capacitors: Replace once every 5 years. 
 
3)  Fuses:  Replace once every 7 years. 
 
4)  Cooling fan: Replace once every 3 years. 
 
 
 
 
 