Westinghouse MA7200 Plus User Manual

Page of 24
               MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual    
__________________________________________________________________ 
________________________________________________________________ 
                                                                                           TECO – Westinghouse Motor Company 
3
Step 2
 -  Apply Power to the Drive 
• Apply AC power to the Inverter and observe the LCD Display Line 1; it should read 
  “Freq. Cmd 000.00Hz”. Line 2 should read “TECO”. The red LED on the STOP key should be on.  
  The DRIVE and FWD LED’s should be on. (See Fig. 1 below) 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Step 3
 - Set Drive to Run Mode 
• If the red DRIVE LED is not on with AC power up, press the PGRM / DRIVE key until the red  
  Drive LED is on. The Inverter is now in the RUN mode. 
 
Step 4
 - Check Fan or Pump Motor Operation 
• 
Enter 10.00Hz for the frequency reference and set parameter Sn-08 = 1  to disable Reverse
 
Direction Operation. NoteThe output from the inverter is displayed in Hz as factory default. If 
desired, the output may be displayed in other units such as (%) of full speed, PSI etc. (see 
 Step 9)