APC SMX3000RMLV2UNC User Manual

Page of 20
Smart-UPS X 2000/2200/3000 VA  
12
Network Management Card Settings 
These settings are available only on units that have a Network Management Card (NMC). 
•  NMC IP Address Mode
•  NMC Default Gateway
Turn Off Delay
90 sec
Set the value in 
seconds
The amount of time that the Switched Outlet 
Groups will wait between receiving the command 
to turn off and the actual shut down.
Reboot Duration 8 sec
Set the value in 
seconds
The amount of time that the Switched Outlet 
Groups must remain off before it will restart.
Minimum Return 
Time
0 sec
Set the value in 
seconds
The amount of battery runtime that must be 
available before the Switched Outlet Groups will 
turn on again after a shutdown.
Load Shed On 
Battery
Disabled
• Shutdown with 
Delay
• Shutdown 
immediately
• Turn off 
immediately
• Turn off with delay
• Disabled
When the unit switches to battery power, the UPS 
can disconnect power to the Switched Outlet 
Groups to save runtime.
Configure this delay time, use the
 L
OAD
 S
HED
 
T
IME
 
WHEN
 O
N
 B
ATTERY
 setting.
Load Shed Time 
when On Battery
Disabled
Set the value in 
seconds
The amount of time the outlets will function on 
battery power before they will turn off.
Load Shed On 
Runtime
Disabled
• Shutdown with 
delay
• Shutdown 
immediately
• Turn off 
immediately
• Turn off with delay
• Disabled
Configure this time using the 
L
OAD
 S
HED
 
R
UNTIME
 R
EMAINING
 setting.
Load Shed On 
Runtime 
Remaining
Disabled
Set the value in 
seconds
When the remaining runtime reaches this level, 
the Switched Outlet Groups will turn off.
Load Shed on 
Overload
Disabled
• Disabled
• Enabled
In the event of an overload (greater than 105% 
output), the Switched Outlet Groups will 
immediately turn off to conserve power for 
critical loads. The Switched Outlet Groups will 
only turn on again with a manual command.
Function
Factory Default Options
Description