Installation
MGE™ Galaxy™ 3500
10-40 kVA 380/400/415 V with batteries
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
Warning: ALL safety instructions in the Safety Sheet 
(990-2940) must be read, understood, and followed when 
installing the UPS system. Failure to do so could result in 
equipment damage, serious injury, or death.
Warning: After the UPS has been electrically wired, do 
not start it up. Start-up is commissioned to authorized 
personnel from Schneider Electric.
Caution: All electrical power and power control wiring 
must be installed by a qualified electrician, and must comply 
with local and national regulations for maximum power 
rating.
Note: Ensure that the unit is in its final location prior to 
installation.
Note: Battery and utility/mains power must not be 
connected until all other wiring has been completed.
See Also: For parallel configurations see manual 990-
3568.
Level the Enclosure
Warning: The system must be installed on a level floor. 
The leveling feet will stabilize the enclosure, but will not 
account for a badly sloped floor.
 Use a 13/14 mm wrench to adjust the four leveling feet. 
 Ensure that the system is level.
Caution:  Do not move the enclosure after the leveling feet 
have been lowered.
Floor Anchoring (if applicable)
Anchor the UPS enclosure to the floor
Note: Floor-anchoring bolts are not provided with the UPS. 
Purchase the bolts locally (minimum size: M8). Follow the 
specifications given by the manufacturer of the floor 
anchoring system when bolting the UPS system to the floor.
 Reuse the two transport brackets (one 
on each side) that were used to secure the 
UPS to the pallet during transport.
 Drill two to six holes in the floor for 
each bracket. Attach with bolts.
Prepare for Cables
Bottom cable entry
 From the rear of the UPS, loosen the six 
M4 screws from the upper cover (the cable 
landing area) on the back and remove.
 
Route the cables from the 
slanted back plate, up 
through the punched 
bracket, and into the cable 
landing area.
 Fasten the cables with 
cable ties
Note: A conduit box (part no. SUVTOPT001 or 
SUVTOPT002) is available as an option. 
 UPS
UPS
XR battery enclosure