APC 1000/ VA User Manual

Page of 18
Smart-UPS 750/1000/1500/2200/3000 VA 100/120/230 Vac 500 VA 100 Vac Tower
10
Customize the Main and Switched Outlet Groups
Use the Configuration menus to change the Main Outlet Group and the Switched Outlet Group settings.
Network Management Card Settings 
These settings are available only on units that have a Network Management Card (NMC) and are set at the factory. 
These settings can only be modified using an external interface, such as the NMC Web interface.
•  NMC IP Address Mode
•  NMC IP Address
•  NMC Subnet Mask
•  NMC Default Gateway
Function
Factory Default
Options
Description
Name String 
Outlet Group
Outlet Group 1
Edit these names using an external interface, such as the Network 
Management Card Web interface.
UPS Name String
UPS Outlets
Turn On Delay
0 sec
Set the value in 
seconds
The amount of time the UPS or 
Switched Outlet 
Group
 
will wait between receiving the command to 
turn on and the actual startup.
Turn Off Delay
• 0 sec (UPS Outlets)
• 90 sec (Switched 
Outlet Groups)
Set the value in 
seconds
The amount of time the UPS or 
Switched Outlet 
Group
 
will wait between receiving the command to 
turn off and the actual shut down.
Reboot Duration
8 sec
Set the value in 
seconds
The amount of time the UPS or 
Switched Outlet 
Group
 
must remain off before it will restart.
Minimum Return 
Time
0 sec
Set the value in 
seconds
The amount of battery runtime that must be available 
before the UPS or 
Switched Outlet Group
 
will turn 
on after a shutdown.
Load Shed On 
Battery
Disabled
• Enable
• Disable
When the unit switches to battery power, the UPS 
will disconnect power to the
 
Switched Outlet Group
 
to save battery runtime.
Configure this delay time, use the
 L
OAD
 S
HED
 T
IME
 
WHEN
 O
N
 B
ATTERY
 setting.
Load Shed Time 
when On Battery
1800 sec
Set the value in 
seconds
The amount of time the outlets will function on 
battery power before they will turn off.
Load Shed On 
Runtime
Disabled
• Enable
• Disable
When the battery runtime falls below the specified 
value, the
 
Switched Outlet Group
 
will turn off.
Configure this time using the 
L
OAD
 S
HED
 R
UNTIME
 
R
EMAINING
 setting.
Load Shed On 
Runtime 
Remaining
120 sec
Set the value in 
seconds
When the remaining runtime reaches this level, the
 
Switched Outlet Group
 
will turn off.
Load Shed on 
Overload
Disabled
• Disabled
• Enabled
In the event of an overload (greater than 107% 
output), the
 
Switched Outlet Group
 
will immediately 
turn off to conserve power for critical loads. The 
Switched Outlet Group
 
will only turn on again with 
a manual command.