4.9.  Parameter Objects (0x65) 
Class code 0x65. This object provides VF-MB1/S15’s Parameter access. 
Range Address accessed: 
Input Instance 
Real Logical address in Drive accessed 
0x0001-0xFFFF 0x0001-0xFFFF 
* Refer to "Class Attributes" when the instance is 0. 
* If you want to access the au1, please use the "Application Objects (64 hex)." 
 
Class Attributes 
Instance  Attribute ID  Access 
Name 
Data type
Details 
Value
Get 
Revision   
UINT 
Revision of this object 
2 Get Max 
Instances 
UINT Maximum instance number of an 
object currently created in this class 
level of the device. 
65535
Get 
Number of Instances 
UINT 
Number of object instances currently 
created at this class level of the 
device. 
65535
Get 
Max ID of class 
attributes 
UINT 
The attribute ID number of the last 
class attribute of the class definition 
implemented in the device. 
Get 
Max ID of instance 
attribute 
UINT 
The attribute ID number of the last 
instance attribute of the class 
definition implemented in the device.
 
Class Services   
Service Code 
Service Name 
Description of Service 
0x0E Get_Attribute_Single  Read one attribute 
 
 
Instance 1 Attribute 
Instance  Attribute ID  Access 
Name 
Data type
Details 
See 
below 
3 Get/Set 
parameter 
UINT 
Parameter corresponding to the Instance 
address 
 
Instance Services   
Service Code 
Service Name 
Description of Service 
0x0E Get_Attribute_Single  Read one attribute 
0x10 Set_Attribute_Single  Write one attribute 
 
 
Attribute ID of all parameters are 3. Moreover, about the instance ID of each parameter, it 
becomes "parameter communication number". 
About the details of the contents of a parameter please refer to VF-MB1 instruction 
manual or VF-S15 instruction manual. 
 
Example 1: 
When "ACC. time" is set to 5 s, since the minimum unit is 0.1s, 
5 / 0.1 = 50 = 32H 
Since the communication umber of "Acc. time" is "0009", it writes "32H" is instance ID "0009."