Lantronix 900-510 User Manual

Page of 280
2: Overview 
SLB™ Branch Office Manager User Guide 
 
19 
A system administrator, upon losing IP connectivity to a server, takes the following steps: 
 
Views the server’s Ethernet interface state information provided by the SLB 
branch office manager. 
 
If the Ethernet interface is faulty, connects to the server’s console port by means 
of the SLB web page or CLI (optionally via the SLM management appliance) and 
checks the server’s system parameters. 
 
If the server is not responsive on the console port, commands the SLB branch 
office manager to reboot the server’s power. 
 
If the entire branch office loses IP connectivity, dial in to the SLB device to 
perform the diagnostic functions 
Hardware Features 
The SLB hardware includes the following: 
 
1U-tall (1.75 inch) rack-mountable appliance 
 
2 10Base-T/100Base-TX network ports 
 
1 front panel serial console port for VT100 terminal or PC with emulation 
 
2 PC Card slots 
 
Front panel LCD display and keypad  
 
256 KB-per-port buffer memory for serial device ports 
 
8-port unmanaged Ethernet switch with auto MDI/MDIX function 
 
8 RS-232 serial device ports connected via Category 5 (RJ45) wiring 
 
AC Power Input:  
 
SLB088411-01 model: 
  - (1) IEC-60320/C20 inlet, 100-120 VAC, 50/60Hz  
  - (20A Branch Circuit) 16A max input current
2
  
  - (15A Branch Circuit) 12A max input current
1
  
 
SLB088412-01 model: 
  - (1) IEC-60320/C20 inlet, 100-240 VAC, 50/60Hz  
  - (20A Branch Circuit) 15A max input current  
 
Power Outlets (Total Switched Power): 
 
 SLB088411-01 model: 
  - (4) NEMA 5-15R outlets, 100-120 VAC, 50/60Hz  
  - (20A Branch Circuit) 15A max per outlet, 16A total
2
  
- (15A Branch Circuit) 12A max per outlet, 12A total
1
  
 
SLB088412-01 model    
  - (4) IEC-60320/C13 outlets, 208-240 VAC, 50/60Hz 
  - (20A Branch Circuit) 10A max per outlet, 15A total 
Note: The outlet voltage equals the input voltage. 
 
Convection cooled, silent operation, low power consumption 
Note: 
For more detailed information, see
page 
. 
1
 The max input/output current is de-rated to 12A when using the supplied NEMA 
5-15P (15A) cable (p/n SLPP012310-01).