C: Safety Information 
SLB™ Branch Office Manager User Guide 
 
268 
 
Install only in restricted access areas (dedicated equipment rooms, equipment 
closets or the like) in accordance with Articles 110-16,  
110-17, and 110-18 of the National Electrical Code, ANSI/NFPA 70. 
 
 
Route and secure input wiring to terminal block in such a manner that it is 
protected from damage and stress. Do not route wiring past sharp edges or 
moving parts. 
 
 
Incorporate a readily accessible disconnect device, with a 3 mm minimum contact 
gap, in the fixed wiring. 
 
 
Provide a listed circuit breaker suitable for protection of the branch circuit wiring 
and rated 60 VDC minimum. 
Fuses 
 
For protection against fire, replace the power-input-module fuse with the 
same type and rating. 
Rack 
If rack mounted SLB devices are installed in a closed or multi-unit rack assembly, they 
may require further evaluation by Certification Agencies. The following items must be 
considered: 
 
Do not install the SLB branch office manager in a rack in such a way that a 
hazardous stability condition results because of uneven loading. A drop or 
fall could cause injury. 
 
The ambient temperature (Tma) inside the rack may be greater than the 
room ambient temperature. Make sure to install the SLB device in an 
environment with an ambient temperature less than the maximum operating 
temperature of the SLB branch office manager. (See 
on pag
 
Install the equipment in a rack in such a way that the amount of airflow 
required for safe operation of the equipment is not compromised. 
 
Mount the equipment in the rack so that a hazardous condition is not 
achieved due to uneven mechanical loading.
  
 
Maintain reliable earthing of rack-mounted equipment. Give particular 
attention to supply connections other than direct connections to the branch 
circuit (e.g. use of power strips). 
 
Before operating the SLB device, make sure the SLB branch office manager 
is secured to the rack. 
Port Connections 
 
Only connect the network port to an Ethernet network that supports 10Base-
T/100Base-T. 
 
Only connect device ports to equipment with serial ports that support EIA-
232 (formerly RS-232C). 
 
Only connect the console port to equipment with serial ports that support 
EIA-232 (formerly RS-232C).