4-12
Cisco Nexus 5500 Platform and Cisco Nexus 5000 Platform Hardware Installation Guide
OL-15902-01
Chapter 4      Replacing Components
  Replacing or Installing Power Supplies
Step 6
Verify the power supply operation by checking that the power supply LED is green.
Wiring a DC Power Connector
Warning
A readily accessible two-poled disconnect device must be incorporated in the fixed wiring. Statement 
1022
Warning
This product requires short-circuit (overcurrent) protection, to be provided as part of the building 
installation. Install only in accordance with national and local wiring regulations. 
Statement 1045 
Warning
When installing or replacing the unit, the ground connection must always be made first and 
disconnected last. 
Statement 1046 
Warning
Installation of the equipment must comply with local and national electrical codes. Statement 1074
Warning
Hazardous voltage or energy may be present on DC power terminals.  Always replace cover when 
terminals are not in service.  Be sure uninsulated conductors are not accessible when cover is in 
place. 
Statement 1075
Before installing a DC power supply to the switch, you will need to attach DC connection wires that you 
provide (10 GA recommended) to the DC power connector included in the DC power supply’s accessory 
kit. To wire the connector:
Step 1
Using a 1/8” flat head screwdriver or No. 1 Phillips head screwdriver, loosen the set screws on the 
connector to freely accept the power wires. The connector will accept 8-24 AWG wires, use what your 
local electrical code calls for.
Step 2
Strip 1/2” of insulation off the DC wires you will use.
Step 3
Insert the black (DC negative) wire into the right aperture on the connector and tighten down the 
connection set screw. Finger tight or about 3 ft./lbs should be sufficient.
Step 4
Insert the red (DC positive) wire into the left aperture on the connector and tighten down the connection 
set screw. Do not tighten over 0.7 Nm.