Pelco C1528M-F User Manual

Page of 106
 
C1528M-F (6/05)
27
 
Connecting a Single ALM2064 Alarm Interface Unit
To connect a single ALM2064 Alarm Interface Unit: 
1. Connect the ALM2064 OUT port to COM 3 on the CM6800E using the 6-foot (1.8 m) straight data cable supplied with the CM6800E. 
2. Set SW2, DIP switches 1-8 to the appropriate positions for the local address (default address setting is 1). Refer to the ALM2064 Alarm 
Interface Unit Installation/Operation Manual for instructions.
Figure 19.  Connecting a Single ALM2064 Alarm Interface Unit
1
2
3
4
5
6
7
8
16
8
7
6
32
31
4
3
2
120/230~
50/60 HZ
25 WATTS
  
1 2 3 4 5 6 7 8
CONTROL  
A T
+
T
-
R
+
R
-
T
+
T
-
R
+
R
-
B
1
2
F
3
1
010101
CM6800E-48X8 COM 3
DEFAULT SETTINGS:
M, RS-485, 19200 BAUD,
NO PARITY, 8 DATA BITS,
1 STOP BIT
STRAIGHT CABLE
(SUPPLIED)
RS-485
ALM2064
CONNECT THROUGH
THE "OUT"PORT
ALM2064
RJ-45 PIN-OUTS
CM6800 COM 3
RJ-45 PIN-OUTS
CM6800 COM 3
RJ-45 PIN-OUTS
1   Rx+
2   Rx-
3   NC
4   NC
5   GROUND
6   NC
7   Tx-
8   Tx+
1   Tx+
2   Tx-
3   
4    
5    
6    
7   Rx-
8   Rx+