D e l l   Po w e r C o n n e c t   R P S - 6 0   S e t u p   G u i d e
www
.dell.com | support.dell.com
Mounting Instructions
 NOTICE: Before you install the PowerConnect™ RPS-60, consult the 
User's Guide for your PowerConnect switch to confirm that your switch 
supports the PowerConnect RPS-60 redundant power system.
The PowerConnect RPS-60 is an external redundant power system that 
provides a second redundant power supply for your PowerConnect switch, 
eliminating the power supply as a single point of failure. To use the RPS-60:
1
Attach the adapter tray to the back of the switch by tightening the two 
mounting screws.
2
Insert the power adapter into the tray.
3
Plug the power adapter’s DC cable into the connector labeled "RPS" 
on the back of the switch.
4
Connect the AC power cable to the power adapter, and then plug it 
into an electrical outlet.
The switch is now using both power supplies simultaneously. You can 
monitor the status of the two power supplies with the front-panel LEDs on 
your PowerConnect switch.
Technical Information
Input Characteristics
Input voltage range
90 VAC to 264 VAC, single phase
Input frequency range
47 Hz to 63 Hz
Max. input AC current
1.5 A at 130 VAC; 1 A at 230 VAC
Inrush current (cold start) 
50 A at 115 VAC; 100 A at 230 VAC 
Efficiency
80% minimum at 115-VAC input full load
Output Characteristics
Static output characteristics (Vo)
Output voltage
12 V ± 5%
Load range minimum
0 A
Load range maximum
5 A
Peak (1sec)
6 A