Connecting Customer-Supplied Safety and Power Control Equipment
Adept SmartController User’s Guide, Rev. E
55
User E-Stop Indication - Remote Sensing of E-Stop
Two pairs of pins on the XUSR connector (pins 7, 20 and 8, 21) provide voltage-free 
contacts, one for each channel, to indicate whether the E-Stop chain, as described above, 
on that channel is closed. Both switches are closed on each of the redundant circuits in 
normal condition (no E-Stop). The user may use these contacts to generate an E-Stop for 
other equipment in the workcell. This output does NOT report status of “line E-Stop” 
input (see the section below for more information). The load on the contacts must not 
exceed 40VDC or 30VAC at a maximum of 1A.
These voltage-free contacts are provided by a redundant, cyclically checked, 
positive-drive, safety relay circuit for EN-954-1 Category 3 operation (see 
 and 
 for the customer E-Stop circuitry).
Line E-Stop Input
The XUSR connector on the SmartController contains a two-channel Line E-Stop input for 
workcell or other equipment emergency stop inputs. Generally, the customer E-Stop 
Indication contact outputs are used to cause an emergency stop in such external 
equipment. Thus, if one were to wire the same equipment’s outputs into the customer 
E-Stop input (that is, in series with the local robot’s E-Stop push buttons), a lock up 
situation can occur. 
The Line E-Stop input comes into the circuit at a point where it cannot affect the customer 
E-Stop indication relays and will not cause such a lock up situation. For any situation 
where two systems should be “cross-coupled”, for example, the customer E-Stop 
indication of one SmartController is to be connected to the input of another 
SmartController, the Line E-Stop input is the point to bring in the other SmartController’s 
output contacts, see 
 for more information. 
Do not use the Line E-Stop for such devices as local E-Stop push buttons since their status 
should be reported to the outside on the local customer E-Stop indication output contact 
while the Line E-Stop inputs will not.
Muted Safety Gate E-Stop Circuitry
Two pairs of pins on the XUSR connector (pins 5, 18 and 6, 19) provide connections for a 
safety gate designed to yield an E-Stop allowing access to the workspace of the robot in 
Manual mode only, not in Automatic mode. The E-Stop is said to be “muted” in Manual 
mode (see 
 for the customer E-Stop circuitry).
The muted capability is useful for the situation where a shutdown must occur if the cell 
gate is opened in normal production mode, but you need to open the gate in manual 
mode. In muted mode, the gate can be left open for personnel to work in the robot cell. 
However, safety is maintained because of the speed restriction.
CAUTION: 
If the cell gate must always cause a robot 
shutdown, do not wire the gate switch into the muted 
safety gate inputs. Instead, wire the gate switch contacts in 
series with the user E-Stop inputs.