Emerson 200I/48-NT5C05C User Manual

Page of 62
Specifications   15 
Emerson Energy Systems 
Rectifier 200I/48
NT5C05C   Installation and User Manual 
Table 4 - Ambient conditions for the rectifier 
Operating 
conditions 
A minimum airflow clearance of 2 inches ( 5 cm ) is 
required at the rear of the rectifier. 
The rectifier will operate properly under the following 
conditions. 
Temperature:   32°F to 122°F  ( 0°C to +50°C ) 
32°F to 104°F  ( 0°C to +40°C ) with air 
filters 
Humidity:  
0 to 95% RH ( non-condensing ) at 4 
kPa max. equiv. to 7,000 ft. ( 2,100 m ) 
above sea level 
Transportation 
conditions 
During transportation, the rectifier can be subjected to 
the following conditions without sustaining damage. 
Temperature:   –67°F ( –55°C ) for 16 hours 
140°F  ( +60°C ) dry heat 
Humidity:  
0 to 95% RH ( non-condensing ) at 
4 kPa max. 
Vibration:  
38 mm / s max. ( 10 Hz to 30 Hz ) 
sinusoidal, 18-inch ( 457 mm ) drop 
when packaged 
Pressure:  
12 kPa  min. equiv. to 49,212 ft. 
( 15,000 m above sea level) 
Temperature shock : 
58°F to 140°F  ( 
50°C to 60°C ) 
Storage conditions 
During storage, the rectifier may be subjected to the 
following conditions without damage : 
Temperature:   –67°F ( –55°C ) for 16 hours to 140°F  
( +60°C ) dry heat 
Humidity:  
0 to 95% RH ( non-condensing ) at 
4 kPa maximum 
The rectifier contains aluminum electrolytic capacitors 
that have a shelf life of five years or greater at the 
maximum rated storage temperature.