Procedure 5 - Cabling the ac input to the NT5C05CA / CB rectifiers 
Step Action 
Install the ac breaker ( 30 A / 3 phase per rectifier ) in the 380 / 
415 volts ac service panel and lock it in the open ( OFF ) position. 
Put the ac breaker to OFF. 
Run the ac armored cable ( metric no. 25 [ 10 AWG ] 3 conductors 
and ground ) from the service panel, through the top of the cabinet, 
to the rear of the rectifier. 
Secure the ac cable to the side of the cabinet using cable ties and 
adhesive anchors. Make sure the cable are located in a manner that 
will not interfere with the insertion of the rectifier ( see Figure 6 ). 
Ground the conduit sheath to the ac service panel. Insulate the 
conduit connector at the rectifier end with electrical tape to isolate it 
from the ac ground. 
Remove the two ac protection plates located at the rear of the 
rectifier. 
Strip 10 inches ( 250 mm ) of armored insulation from the end of the 
ac cable. Insert the wires in the 90
°
 conduit connector ( see Figure 
7 ). 
Run the signal cable from the rectifier to the interconnect board or 
controller as described in the "Control signal connections" section. 
Connect the green ground wire to the FR GND terminal. 
10 
Connect the power leads to the L1, L2 and L3 terminals ( any phase 
sequence ) ( see Figure 7 ). 
11 
Tighten the elbow connector and reassemble the ac protection plate. 
12 
Run the signal cable from the rectifiers to the interconnect board or 
controller as specified in the " Connecting the control signals" 
section. 
13 
Secure the signal cables to the insulating busbar support, located in 
the cabinet, with cable ties. 
14 
Start-up the rectifier as described in the “ Start-up “ procedure. 
end