Emerson 200I/48-NT5C05C User Manual

Page of 62
Installation   29 
Emerson Energy Systems 
Rectifier 200I/48
NT5C05C   Installation and User Manual 
Procedure 8 - Connecting an NT5C05CC rectifier directly to a controller 
Step Action 
If an NT6C43PB interconnect board is not available, each rectifier 
must be connected directly to the controller with the following 
cables : 
• 
P0723784, P0723785 or P0723786 ( for conventional 
controllers ) 
• 
P0723708, P0723709 or P0723210 ( for front access 
controllers ) 
end
 
For controllers not manufactured by Emerson Energy Systems see Table 
12 in the " Functional Description " chapter describing the pin assignments 
of the rectifier. Refer to Table 8 for the pin assignments of connectors J7 
to J12 on board NT6C43PB. 
Note: 
The alarm and control signals in Table 8 are all ground 
signals except for the RC– signal that is a –48 V 
battery signal. 
Table 8 - Pin assignment for connectors J7 to J12 
Pin Label 
Function 
Input/ 
Output 
EQL Equalize 
Input 
RG+ Remote 
sense 
Input 
RC– Remote 
sense 
Input 
FAN ALM  Fan fail alarm 
Output 
HVSDR 
High voltage shutdown reset 
Input 
HVSD 
High voltage shutdown 
Input 
RFA 
Rectifier failure alarm 
Output 
TR Temporary 
release 
Input 
3.7.1.  Monitoring of the shunt current 
A 12-pin connector ( J13 ) is also available on the NT6C43PB 
interconnect board for monitoring the individual output current shunt 
readings ( 250 A / 50 mV for example ) of each rectifier in a cabinet or a 
frame ( see Table 9 ).