36   Functional description 
UM5C05C   P0745680   Standard 6.00   October 2001 
Emerson Energy Systems 
Table 11 - Adjusting the potentiometers and switches 
Potentiometers Description 
CL ADJ 
Current limit adjust ( 100 A to 210 A ) 
CUR CAL 
Current reading calibration 
EQL ADJ 
Equalize voltage adjust ( 0 V to 
4 V ) 
FLT ADJ 
Float voltage adjust ( 
46 V to 
58 V ) 
HVSD ADJ 
High voltage shutdown adjust ( 
52 V to 
60 V ) 
VOLT CAL 
Voltage reading calibration 
Switches Description 
EQL / FLT 
Equalize / Float selection switch 
SLS / FS 
Slope load sharing / Forced load sharing selection 
ST UP DELAY 
Start-up delay selection DIP ( 4 sec to 2 min ) 
VOLT / AMP 
Voltage and current display selection switch 
Table 12 - Rectifier input / output signals to the controller 
Designation Description 
RG+ / RC
 
External reference voltage across the batteries 
measured through the controller to regulate the voltage. 
HVSD 
Remote High Voltage Shutdown input activated by a 
BAT RTN signal. 
HVSDR 
Remote High Voltage Shutdown Reset input activated by 
a BAT RTN signal. 
TR 
Remote Inhibit input activated by a BAT RTN signal. 
EQL 
Remote Equalize input activated by a BAT RTN signal. 
RFA 
Rectifier Failure Alarm output activating a form C contact 
F ALM 
Fan Failure Alarm output activating a form C contact 
SHUNT ( + ) and 
SHUNT ( 
 ) 
Rectifier Current input / output ( 50 mV / 250 A ) 
CURRENT 
SHARE 
Common Forced Current Share Mode ( 0-12 V ) 
4.2.5.  Voltage / current display
test and measurement 
CUR CAL / VOLT CAL potentiometers 
These potentiometers are used to calibrate the digital display meter for 
current and voltage measurements. As the two potentiometers affect each 
other, current calibration must be performed before voltage calibration.