Maintenance   51 
Emerson Energy Systems 
Rectifier 200I/48
NT5C05C   Installation and User Manual 
Procedure 11 - Calibrating the meter 
Step Action 
Make sure the remote sense leads are disconnected by removing 
the corresponding RC
 fuse from the controller. 
Set the VOLT/AMP switch to AMP. Set the output load of the plant 
so the rectifier delivers a current of approximately 100 A. Measure 
the voltage between VOUT+ and VOUT
 −
, located on the front panel, 
with a digital meter. 
Convert this measured voltage to a current value ( 50 mV 
corresponding to 250 A ). 
current  =   250 A 
voltage   50 
mV 
If the voltage measured is 20.2 mV : 
measured current 
=   250 A X ( 20.2 mV ) = 101 A 
50 mV 
Rotate the CUR CAL potentiometer on the display panel until this 
value is displayed. 
Put the VOLT / AMP switch to VOLT. Adjust the V CAL 
potentiometer so that the reading displayed on the meter of the 
rectifier is identical to the reading on the digital meter. 
Put the rectifier to OFF and reconnect the sense leads. 
end
 
6.4. 
Resetting the rectifier after an HVSD ( high voltage shutdown ) 
To reset the rectifier after an HVSD condition has occurred execute one of 
the steps contained in Procedure 12. 
Procedure 12 - Resetting the rectifier after a high voltage shutdown 
Step Action 
Locally 
Toggle the ac circuit breaker on the unit itself, or the associated ac 
breaker in the distribution panel OFF and ON ( wait until the green ac 
ON LED extinguishes before toggling the breaker back to ON ). 
Remotely 
Apply a ground signal at the HVSDR input of the rectifier. 
end